Revolution Series Single-Stage Water-to-Water Geothermal System

Revolution ws
Revolution
Warranty badge

Hydron Module single-stage water-to-water models deliver maximum efficiency and maximum comfort in a compact package. Plus, they're built to the high standards of quality and craftsmanship for which Hydron Module is known. It is the ultimate solution for increased efficiency, reduced heating and cooling costs, unsurpassed comfort and exceptional reliability.

Applications

Radiant Heat Hot Water Snow Melt

Features

  • Radiant floor ready
  • Flow switch protected
  • Optional hot water generator (desuperheater)
  • Copeland® UltraTech® two-stage scroll compressor
  • Digital controls
  • Oversized copper coaxial heat exchangers
  • Rugged powder coated cabinet
  • Insulated refrigerant circuit
  • 1" FPT fittings

Performance Data

WS036

Cooling
Full Load BTU
34,700
EER
18.2
Part Load BTU
0
EER
0.0
Heating
Full Load BTU
26,600
COP
3.1
Part Load BTU
0
COP
0.0

WS048

Cooling
Full Load BTU
52,800
EER
17.7
Part Load BTU
0
EER
0.0
Heating
Full Load BTU
42,100
COP
3.1
Part Load BTU
0
COP
0.0

WS060

Cooling
Full Load BTU
60,000
EER
17.1
Part Load BTU
0
EER
0.0
Heating
Full Load BTU
53,000
COP
3.1
Part Load BTU
0
COP
0.0

WS072

Cooling
Full Load BTU
73,300
EER
17.7
Part Load BTU
0
EER
0.0
Heating
Full Load BTU
63,100
COP
3.4
Part Load BTU
0
COP
0.0

WS084

Cooling
Full Load BTU
83,600
EER
16.1
Part Load BTU
0
EER
0.0
Heating
Full Load BTU
74,200
COP
3.1
Part Load BTU
0
COP
0.0
  • Rated in accordance with ISO Standard 13256-2, which includes pump penalties.
  • Heating capacities based on 32°F EST & 104°F ELT.
  • Cooling capacities based on 77°F DB, 53.6°F ELT.
  • Entering load temperature over 120°F heating and under 45°F Cooling is not permissible.
  • Floor heating is most generally designed for 85°F entering load temperature.

Literature

Accessories

"A" coil (hydronic)

Hydronic a coil

The specially matched "A" coil allows the split geothermal system to be added to an existing air handler or furnace in retrofit applications. Additionally, the "A" coil can allow the system to operate in a dual-fuel application where backup heat is supplied by a traditional furnace.

Air handler (hydronic)

Air handler

These multi-positional air handlers are specially matched to our split systems for maximum performance. The match also qualifies the system for the 30% U.S. federal tax credit. The air handler can be installed in remote parts of the home, or hard to reach areas where space is at a premium.

Programmable thermostat

Programmable thermostat

Keeps the home more comfortable by operating the unit on a set schedule and temperature range. This also saves on energy costs by setting the unit back while the home is unoccupied.

Non-programmable thermostat

Non programmable thermostat

Designed to take maximum advantage of the multi-stage functionality of the unit. This allows the unit to achieve maximum savings by only operating at the right range to match the current weather.

Flow centers - pressurized

Pressurized flow center

Circulates the fluid through the unit and the geothermal loop field. These types form a completely closed system.

Unit air pad (plastic or foam)

Air pad

The unit air pad creates a buffer between the unit and the home. This buffer prevents any vibration from the unit to be transmitted into the home which improves the already quiet operation of the unit.

Consumer purchase plans

Purchase plan

With a wide variety of payment options and terms, our consumer payment plans make installing a geothermal system easier and more cost effective. By deferring your initial payments out, you can start enjoying your new system earlier and take time to obtain many of the various rebates and tax credits offered.

Disposable pleated filter

Pleated filter

This type of filter uses a pleated media to remove dust and other particles from the air stream. It is important to check these filters regularly and replace them as needed.

Electrostatic filter (washable)

Electrostatic filter

This type of filter is a permanent media filter that can be washed from time to time as needed. This eliminates the need to buy new filters.

Electronic 24 volt air cleaner

24v electrostatic filter

This type of filter uses an electrically charged media to increase filtration performance. This improves indoor air quality by removing more particles from the airstream. This filter requires the occasional media replacement.

EWC zone control

Zone control

These highly sophisticated controls work with dampers in the ductwork to create multiple zones throughout the house. You can utilize one unit, but have different temperatures in each zone. The control panel controls both the unit, and the zone dampers.

Flow center - non-pressurized

Non pressure flow center

Circulates the fluid through the unit and the geothermal loop field. This type of system uses an expansion tank that can be topped off should the loop require it due to thermal expansion.

Auxiliary external electric heater

External heater

Adds that little bit of extra heat on those few coldest days. Also helps to balance the system size by balancing out those few extreme days. These heaters are installed in the supply air duct outside of the unit. Mostly used on horizontal style equipment.